Sampling and Shipping
Generally, microbiological culture tests are started as soon as possible after collection, so shipping overnight is preferred. We recommend shipping the sam...
Thu, 19 Dec, 2019 at 8:49 AM
If overnight shipping is not possible on the collection day, samples should be refrigerated at (2-8°C) until they are ready to be shipped.
Wed, 18 Dec, 2019 at 2:41 PM
Each bottle has an expiration date printed on a sticker attached near the top of the bottle and cap. It is typically 2 years from the date the bottles were ...
Wed, 18 Dec, 2019 at 2:44 PM
Organism/ Test Holding Time Legionella ≤2 days Pseudomonas aeruginosa ≤30 hours Stenotrophomonas maltophilia, Acinetobacter spp., Burkholderia ...
Mon, 25 Jan, 2021 at 3:33 PM
Swabs should primarily be used during a case investigation in conjunction with water samples from the same sites. Swabs should not be used on cooling towers...
Wed, 18 Dec, 2019 at 2:57 PM
Depending upon sample type and processing methods, sample storage could vary from 3 days up to two weeks (space permitting).
Tue, 24 Mar, 2020 at 8:16 AM
The culture test will determine how effectively the biocide treatment is working because the sample comes directly from the treated water in a cooling tower...
Wed, 18 Dec, 2019 at 3:02 PM
First draw hot water represents the worst-case microbiological quality and has the best chance to recover Legionella if present. First draw hot water answ...
Wed, 18 Dec, 2019 at 3:05 PM
Call us for laboratory services pricing at 412-281-5335 Click here to book a meeting with our sales team Click here to start testing
Mon, 25 Jan, 2021 at 2:15 PM
On the left-hand side of your MySPL dashboard, under the More section, click the link titled Sampling & Shipping. This link will include sampling guide...
Fri, 16 Oct, 2020 at 2:20 PM